Modbus TCP / PROFINET Gateway

GT200-PN-MT

2.0

GT200-PN-MT 2.0 Quick Start Guide

Product Appearance

Wiring

  • 1. 1.35mm DIN Rail Installation.
  • 2. Connect the gateway power interface to the power supply.
    Pin Function
    1 Power GND
    2 NC(Not Connected)
    3 24V+,DC Positive 24V
  • 3. Connect the Gateway’s RJ45 interface to the computer with a RJ45 cable.
  • 4. Power on the gateway. Run the SST-EPN-CFG to start the gateway configuration.

LED Status Indicators

Indicators Status Description
MS Solid Green Startup completed
Flashing Red (lasts 3 seconds) Locate Function
PMS Solid Green PROFINET connection is established
Flashing Red (lasts 3 seconds) Start-up state, waiting to initialize
PNS Solid Green Establish a connection with the PLC and communicate normally
Solid Red Network cable not plugged in
Flashing Red (1Hz) Initialize completed, not established a connection with the PLC
Flashing Red (2Hz) Initialize completed, not established a connection with the PLC
ENS
Modbus TCP Client Mode
(Modbus TCP network status indicator)
Solid Green Modbus TCP all node connections have been established
Flashing Green Quickly
(500ms on, 500ms off)
Modbus TCP connection is not established
Flashing Green Slowly
(1700ms on, 300ms off)
Modbus TCP Some nodes have been connected
(Not all nodes have been connected)
Flashing Red (lasts 3 seconds) Node disconnection
Flashing Red All nodes are disconnected (failed to establish connection)
ENS
Modbus TCP Server Mode
(Modbus TCP network status indicator)
Solid Green Modbus TCP connection established
Flashing Green Modbus TCP connection is not established
Flashing Red (lasts 3 seconds) Node disconnection

Software Configuration

  • 1. Run the SST-EPN-CFG software installed on your computer.
  • 2. Click "PROFINET" in the tree view on the left, set the network configuration.
  • 3. Click "Modbus TCP" in the tree view on the left and set the Modbus TCP communication parameters.
  • 4. Add node and commands under the "Modbus TCP".
  • 5. Click download button, select the GT200-PN-MT model and then click on "Download".
For more information, please refer to the GT200-PN-MT manual.

Communication Instructions

  • 1. Connect Ethernet cable to gateway's PROFINET interface.
  • 2. Connect Modbus TCP devices to the gateway's Ethernet interface. Please refer to the gateway manual for specific connection methods.
  • 3. Observe the indicator lights to check the communication status.