Serial / PROFIBUS DP Converter

GT100-DP-RS

GT100-DP-RS Quick Start Guide

Product Appearance

Wiring

  • 1. 1.35mm DIN Rail Installation.
  • 2. Connect the gateway power interface to the power supply.
    Pin Function
    1 Power GND
    2 NC(Not Connected)
    3 24V+,DC Positive 24V
  • 3. Refer to wiring of the PROFIBUS DP interface.
    Pin Function
    3 PROFI_B, Data+
    5 GND
    8 PROFI_A, Data-
  • 4. Connect the Gateway’s Type-B interface to the computer with a USB cable.
  • 5. Power on the gateway. Run the SST-MP-CFG to start the gateway configuration.

LED Status Indicators

Indicators Status Description
PBF Solid Red PROFIBUS DP communication fails
Off Normal data communication
STA Flashing Green PROFIBUS DP is communicating
OFF No data communication
TX Flashing Green Serial port is sending data
Off No data sending
RX Flashing Green Serial port is receiving data
Off No data receiving

DIP Switch or Function Button

  • The DP address and mode setting button is located on the top of the GT100-DP-RS. It's used to set the PROFIBUS DP address and operating mode.

Software Configuration

  • 1. Run the SST-MP-CFG software installed on your computer.
  • 2. Click "Fieldbus" in the tree view on the left, set the "PROFIBUS Address" and other parameters.
  • 3. Click "Subnet" in the tree view on the left and set the serial communication parameters.
  • 4. Add serial node and commands under the subnet.
  • 5. Click download button, select the correct serial port number and then click on "Download".
    Note: The software automatically scan the available serial port of system, and the available serial can be shown in serial list.
For more information, please refer to the GT100-DP-RS manual.

Communication Instructions

  • 1. Connect serial devices to the gateway serial interface. There are two different interfaces, RS232 or RS485. Please refer to the gateway manual for specific connection methods.
  • 2. Observe the indicator lights to check the communication status.